How it is worked out
Three-phase: amps = kVA × 1,000 ÷ (1.732 × volts)
Single-phase: amps = kVA × 1,000 ÷ volts
A worked example
A 75 kVA three-phase transformer at 480 volts: 75,000 ÷ (1.732 × 480) is 90.2 amps.
Good to know
- This is the nameplate full-load current. Sizing conductors and protection from it is a code calculation.
How we know this calculator is right
Before this calculator went on the site, 3 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.
See every check
| Numbers used | Result | Worked out separately | This calculator |
|---|
What this proves: the calculator does the arithmetic of the formula shown, correctly. What it cannot prove: your measurements, or figures such as coverage per bag, waste and spacing, which are typical starting values you can change. Go by the product label and your local code.