How it is worked out
BTU per hour = 1.08 × CFM × temperature difference
The 1.08 comes from the weight of air and the heat it takes to warm it, for air at sea level and normal room conditions.
A worked example
Four hundred CFM with a 20 degree split is 1.08 × 400 × 20, which is 8,640 BTU per hour, or 0.72 tons.
Where this turns up
- Checking what a furnace is really putting into the air, from the measured airflow and temperature rise.
- Working backwards to airflow. If you know the furnace output and the temperature rise, CFM is output ÷ (1.08 × rise).
- Finding how much heating a ventilation fan adds to the load when it brings in cold outside air.
This is sensible heat only, the part you can measure with a thermometer. Air conditioning also removes moisture, which is latent heat, so the total cooling is higher than this figure. At altitude the 1.08 is lower.
Common questions
What split should I expect?
Many technicians look for roughly 16 to 22 degrees across a cooling coil, but it depends on humidity and airflow. Follow the equipment data.